Projects & Gallery
Refrigeration and Compressor Engineering Projects
A selection of recent work by the Ref-Tas Ltd team, from Bitzer screw and reciprocating compressor overhauls to marine refrigeration servicing, compressor replacements and the commissioning of industrial plant – onshore and offshore.
- Compressor overhauls
- Marine & offshore service
- Repair & commissioning
Jump to a project
01Industrial refrigeration·Commissioning
Freeze Dryer Repair and Commissioning
Our engineers repaired and commissioned a freeze dryer used for processing fruit and vegetables. To allow testing and commissioning to go ahead, the team repaired the unit’s existing compressor – the make of which could not be identified – and restored it to working order as a temporary measure.
The system performed well throughout testing. The next stage is to replace the temporary compressor with a Bitzer compressor for dependable, efficient long-term operation.
Project highlights
- Existing compressor repaired and returned to operation
- Testing and commissioning completed successfully
- Replacement with a Bitzer compressor planned as the next stage
02Compressor overhaul·Chiller
Overhaul of Two BITZER CSH7563-80Y Compact Screw Compressors
We overhauled two BITZER CSH7563-80Y compact screw compressors, returning both to optimal operating condition. The work followed the manufacturer’s recommended maintenance procedures to improve reliability and efficiency and extend the compressors’ service life.
A properly executed overhaul like this reduces the risk of unplanned downtime, supports energy efficiency and helps the chiller deliver consistent performance.
Scope of work
- Full dismantling and inspection of both compressors
- New rotor sets, built-in motors and bearings
- Replacement discharge flanges and discharge flange covers
- New seals, gaskets and O-rings
- Cleaning of internal components and oil passages
- Reassembly with genuine replacement parts
03Compressor overhaul·Installation
BITZER Compact Screw Compressor Overhaul
Another Bitzer compact screw compressor fully overhauled by our team. Every critical component was inspected and restored to deliver reliable performance and a longer service life.
With the overhaul complete, the compressor was prepared for installation and commissioning, ready to return to dependable cooling duty.
Project highlights
- Complete overhaul of a Bitzer compact screw compressor
- Inspection and restoration of all critical components
- Prepared for installation and commissioning
04Case study·Failure assessment
BITZER CSH8573-110Y: The Cost of Poor Workmanship
High-value industrial equipment should never end up as scrap because of poor workmanship – yet that is exactly what happened to this Bitzer CSH8573-110Y screw compressor after it was overhauled by personnel without the necessary competence.
The compressor showed several critical errors that have no place in professional compressor servicing. As a result, it could no longer be returned to service and was destined for scrap.
The lesson is clear: expertise, the correct tools and strict adherence to manufacturer standards are essential. Cutting corners on critical equipment does not save money – it multiplies the losses. Always make sure the work is carried out by qualified professionals.
What went wrong
- Incorrect bearings fitted, compromising performance and reliability
- Motor rewound and insulated far below acceptable standards
- Grooved nuts loosened and tightened with a hammer and chisel, causing mechanical damage and misalignment
05Compressor overhaul·Industrial cooling
BITZER CSH8593-140Y Overhaul for a Plastic Recycling Plant
Our team completed a full overhaul of a Bitzer CSH8593-140Y compact screw compressor for the central cooling system of one of Nigeria’s leading plastic recycling companies.
The work combined precise mechanical restoration with rigorous testing and quality assurance checks. Installation on site is being carried out by our own well-trained, highly skilled technicians.
Project highlights
- Full overhaul of a Bitzer CSH8593-140Y compact screw compressor
- Mechanical restoration, testing and quality assurance
- Central cooling system for a plastic recycling plant in Nigeria
- Installation by Ref-Tas technicians
06Compressor overhaul·Offshore
BITZER CSH8573-140Y Overhaul for an Offshore Pipe-Laying Barge
We completed a full overhaul of a Bitzer CSH8573-140Y compact screw compressor for the central cooling system of an offshore vessel – one of the harshest operating environments for refrigeration equipment.
As with every overhaul, the work combined precise mechanical restoration with rigorous testing and quality assurance. Our technicians are also responsible for installing and servicing two units on board the client’s offshore pipe-laying barge.
Project highlights
- Full overhaul of a Bitzer CSH8573-140Y compact screw compressor
- Central cooling system for an offshore vessel
- Installation and servicing of two units on board a pipe-laying barge
07Compressor overhaul·Service report
BITZER 6F.2 Reciprocating Compressor Overhaul
This Bitzer 6F.2 compressor arrived at our Ref-Tas service centre after the customer reported that it was not operating correctly. Dismantling the unit revealed contaminated oil, a damaged cylinder head pin and foreign particles from a wire-brush head inside the compressor.
Our technicians carried out a complete overhaul, restoring the compressor to a clean, reliable condition ready to return to service.
Findings
- Contaminated oil throughout the crankcase
- Damaged pin on the cylinder head marked CR
- Wire-brush fragments, one lodged between the suction reed and valve plate and stopping the valve from working properly
Work carried out
- Compressor fully disassembled
- All components flushed and thoroughly cleaned
- Damaged parts repaired or replaced as required
- New gasket kit fitted
- Unit reassembled and professionally repainted
08Marine refrigeration·Service & repair
Onboard Cooling System Repairs – Navy Vessel DB Abuja
Our team carried out a full inspection, service and repair of three refrigeration systems on board the Navy vessel DB Abuja: the central cooling system, the chiller room and the freezer room, all running on Bitzer compressors.
All three systems are now operating reliably and efficiently, maintaining the mission-critical cooling and cold storage the vessel depends on.
Scope of work
- Full nitrogen pressure testing, with all leaks located and sealed
- Replacement of the components needed for long-term system integrity
- New Bitzer BSE32 compressor oil
- All filter driers and pressure gauges replaced
- Pressure switches tested and faulty units replaced
- Deep vacuum before refrigerant charging
- Recharged with R407C (central A/C and vegetable room) and R404A (freezer room)
- Electrical control panels inspected and corrected, with a new temperature controller and sensor
- New Bitzer seawater-cooled condenser installed for the freezer room
09Marine refrigeration·Compressor replacement
BITZER CSH9571-240Y Compressor Replacement on a Marine Vessel
Our Marine Service Team replaced a faulty Bitzer CSH9571-240Y compressor (made in China) with a German-manufactured Bitzer CSH9573-240Y, improving reliability and long-term performance for the client’s marine operations.
Every stage was handled by our experienced technicians, from diagnostics to commissioning. The system was tested and is running satisfactorily.
Scope of work
- Factory-fill B 320 SH oil replaced with 30 litres of BSE170, as recommended for R-407C
- Non-functional oil safety switch identified and corrected during installation
- Damaged insulation on a power supply cable corrected
- System flushed with nitrogen and pressure tested
- Core filter driers replaced
- System evacuated, charged with refrigerant and fully tested
10Compressor overhaul·12-month warranty
BITZER CSH9553-180Y Screw Compressor Overhaul
We carried out a complete overhaul of a BITZER CSH9553-180Y semi-hermetic screw compressor, restoring it to peak performance. After full disassembly and precision inspection, critical components were replaced, and the unit was thoroughly cleaned, realigned and given a protective repaint.
The compressor now operates with renewed efficiency and reliability, and the overhaul is backed by a 12-month warranty.
Scope of work
- Full disassembly and precision inspection
- New bearings, seals, piston rod and built-in motor
- Replacement pressure control valve and gaskets
- Thorough cleaning and realignment
- Protective repaint, backed by a 12-month warranty
Need a compressor overhaul or refrigeration repair?
Speak to the Ref-Tas team about your compressor, chiller or cooling system.